The Model 6200 is a hand-held
portable appliance tester, performing four functions
to ensure the Safety of ClassI, ClassII and ClassIII
230V appliances. And also can measure the mains
voltage.
Readings are displayed on a large liquid crystal
display (LCD) below which are eight LEDs which
unambiguously display a pass or fail indication
for threshold values dictated by DIN VDE 0701/0702
This instrument is suitable
for performing tests as required by the following
standards.
DIN VDE 0701-1 (240):2000 Repairing, modification
and testing of electrical equipment
DIN VDE 0702 : 1995 Periodic inspection for electrical
equipment
RPE 20O+ / 20O-
Protective Conductor Test
RINS 200MO
Insulation Resistance
IEL 20mA
Equivalent Leakage Current
Measuring
Range
0~19.99O
Measuring
Range
0~19.99/
199.9MO
(2ranges auto)
Measuring
Range
0~19.99mA
Range
0~19.99/0~199.9MO
(2ranges auto)
Resolution
of
Measurement
10mO
Resolution
of
Measurement
10kO/
100kOV
Resolution
of
Measurement
0.01mA
Short
Circuit
Current
200~250mA
DC
Rated
Voltage
>500V DC
(+50%/-0%)
Measuring
Voltage
30V AC
Rated Current
>1mA
Internal
Resistance
(RA Meter)
2kO
Open Circuit
Voltage
±5.0±0.4V
DC
Short Circuit
Current
14mA(max.)
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
IL
2mA
Contact Current
VOLT
AC Voltmeter
Measuring
Range
0~1.999mA
Measuring
Range
180~260V
(50/60Hz)
Resolution
of
Measurement
0.001mA
Resolution
of
Measurement
1V
Internal
Resistance
(RA Meter)
2kO
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
General
Supply Voltage
230V±10%
Frequency
50/60Hz±1%
Dimension
185 ( L)×
167 (W) × 89 (D) mm
Weight
1kg
Applicable
Standards
IEC 61010-1
CAT.III 300V,
Pollution Degree2
IEC 60950
Safety of
Information Technology Equipment
IEC 61326-1
EMC requirements
Accessories
7125(Power
Cord (EU)) 7129(Test
Leads with Alligator Clip) 7101(Flat
Test Bar)
Probe Case
Shoulder Strap
Instruction Manual
6201A
Portable
Appliance Testers
The KEW 6201A is a portable
appliance tester, performing four functions to
ensure the Safety of ClassI and ClassII appliances.
And also can measure the mains voltage.
Readings are displayed on a large liquid crystal
display (LCD) below which are four LEDs which
unambiguously display a pass or fail indication
for threshold values dictated by AS/NZS 3760.
This instrument is suitable
for performing tests as required by the following
standards.
AS/NZS 3760:2003 In-service safety inspection
and testing of electrical equipment.
RPE 20ohms
Protective Conductor Resistance Test
RINS 200Mohms
Insulation Resistance Test
Measuring
Range
0~15.00
ohms
Rating
250V/20MO
500V/20M
Measuring
Range
0~19.99M
Resolution
of
Measurement
10m ohms
Resolution of
Measurement
10k
Open Circuit
Voltage
< AC 12V
Output Voltage
250V DC
(+20%/-10%)
@1M
500V DC
(+20%/-10%)
@1M
Measuring
Current
10A AC nominal
value
Short Circuit Current
2.5mA
DC or less
Accuracy
±(3%rdg
+ 5dgt)
Accuracy
±(2%rdg
+ 3dgt)
Leakage
Current Test
AC
VOLT Mains Voltage Check
Measuring
Range
AC 0.1~19.99mA
Measuring
Range
207~264V
Resolution
of
Measurement
0.01mA
Resolution
of
Measurement
1V
Examination
time
Max 15 seconds
Accuracy
±(3%rdg + 5dgt)
Accuracy
±(2%rdg
+ 3dgt)
General
Supply Voltage
240V±10%
Frequency
50Hz±1%
Dimension
185 (L) ×
167 (W) × 89 (D) mm
Weight
1.2kg (only
the instrument body)
Applicable
Standards
IEC 61010-1
CAT.III 300V
Pollution Degree2
IEC 61326-1
EMC requirements
Accessories
7123(Power
Cord (AU)) 7129(Test
Leads with Alligator Clip) 7101(Flat
Test Bar)
7140(Adapter for Extension Cord)
Probe Case
Shoulder Strap
Instruction Manual
6202
``
Portable
Appliance Testers
The Model 6201 is a hand-held
portable appliance tester, performing four functions
to ensure the Safety of ClassI, ClassII and ClassIII
240V appliances. And also can measure the mains
voltage.
Readings are displayed on a large liquid crystal
display (LCD) below which are three LEDs which
unambiguously display a pass or fail indication
for threshold values dic-tated by AS/NZS 3760
This instrument is suitable
for performing tests as required by the following
standards.
AS/NZS 3760:2001 In-service safety inspection
and testing of electrical equipment
RPE 20O+ / 20O-
Protective Conductor Test
RINS 200MO
Insulation Resistance
IEL 20mA
Equivalent Leakage Current
Measuring
Range
0~19.99O
Measuring
Range
0~19.99/
199.9MO
(2ranges auto)
Measuring
Range
0~19.99mA
Resolution
of
Measurement
10mO
Resolution
of
Measurement
10kO/
100kO
Resolution
of
Measurement
0.01mA
Short Circuit
Current
200~250mA
DC
Rated
Voltage
>500V DC
(+50%/-0%)
Measuring
Voltage
30V AC
Open
Circuit
Voltage
±5.0±0.4V
DC
Rated Current
>1mA
Internal
Resistance
(RA Meter)
2kO
Short Circuit
Current
14mA
(max.)
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
IL 2mA
Contact Current
VOLT
AC Voltmeter
I LINE
Current Consumption
Measuring
Range
0~1.999mA
Measuring
Range
180~260V
(50/60Hz)
Measuring
Range
0~16A AC
Resolution
of
Measurement
0.001mA
Resolution
of
Measurement
1V
Resolution
of
Measurement
0.01A
Internal
Resistance
(RA Meter)
2kO
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
Accuracy
±(2%rdg
+3dgt)
General
Supply Voltage
230V±10%
Frequency
50/60Hz±1%
Dimension
185 ( L)×
167 (W) × 89 (D) mm
Weight
1kg
Applicable
Standards
IEC 61010-1
CAT.III 300V,
Pollution Degree2
IEC 60950
Safety of
Information Technology Equipment
IEC 61326-1
EMC requirements
Accessories
7125(Power
Cord (EU)) 7129(Test
Leads with Alligator Clip) 7101(Flat
Test Bar)
Probe Case
Shoulder Strap
Instruction Manual